(1) All aboveground double-walled petroleum
storage tank systems must be properly installed in accordance with:
(a) the manufacturer's specifications and/or
recommendations;
(b) the appropriate recommended practices adopted
by reference in ARM 17.57.104; and
(c) Uniform Fire Code Articles 52, 79 and
Appendix II-F, or when applicable, the Uniform Mechanical Code and NFPA 31, and
all local fire code and building code ordinances.
(2) Vaults and special enclosures must be
installed in accordance with Uniform Fire Code Articles 52, 79 and Appendix
II-F, and the conditions set forth in the written approval provided by the
department of justice fire prevention and investigation bureau or the local
fire official with Uniform Fire Code jurisdiction.